RU EN

TIK-CNV converters

TIK-CNV converters

Designed to measure output values from external sensors, convert the values into digital form, and transfer the received information to the external telemechanics and control system;

The main purpose of the device is to operate as part of a distributed system (consisting of the TIK-PLC 896.11 controller, several TIK-CNVs and sensors) and to implement the following functions: сsampling, time synchronization, measurement channel failure detection.

On the basis of samples, the controller can perform advanced diagnostics - construction and analysis of spectra, execution of diagnostic rules;

TIK-CNV also calculates the following parameters of the measured quantity - RMS, amplitude, magnitude (calculated for the input signal as well as for its 1 and 2 derivatives, 1 and 2 integrals), constant value.

Features

  • RS-485 digital output (Modbus RTU protocol), with speed up to 3 Mbit/s;
  • ability to collect samples (as part of a distributed system);
  • measurement channel failure detection;
  • identical location of power supply and RS-485 contacts for all versions;
  • possibility of changing the program filters for high-pass and low-pass filters for the input signal.

Additional photos

specifications

Interface

  • Input signal type
    current 0-21.5 mA (TIK-CNV 1116)
    charge ± 280 pCL (TIK-CNV 1216)
    voltage ± 5 V (TIK-CNV 1316)
    voltage 0-23.5 V (TIK-CNV 1416)
    thermal resistanceе (TIK-CNV 15x6)
  • Output signal type
    RS-485 digital
  • Protocol
    Modbus RTU
  • Supply
    16-30
  • Power consumption, W, not more
    1.5

Design parameters

  • Overall dimensions, mm
    108x12.6x113.6
    98.5x27x58.5
  • Weight, kg, not more than
    0.2
  • Mounting type
    on DIN-rail
  • Protection class
    IP20

Operating parameters

  • Operating temperature range, ºС
    -40...+60

Reliability parameters and manufacturer's guarantees

  • MTBF, hours, not less than
    20 000
  • Warranty service life, months
    18
  • Service life, years, not less than
    10
Service center